• 12kv 630A Load Break Switch Load Breaker
  • 12kv 630A Load Break Switch Load Breaker
  • 12kv 630A Load Break Switch Load Breaker
  • 12kv 630A Load Break Switch Load Breaker
  • 12kv 630A Load Break Switch Load Breaker
  • 12kv 630A Load Break Switch Load Breaker

12kv 630A Load Break Switch Load Breaker

Type: High-voltage
Structure: Three-column Disconnector
Installation: Indoor High-voltage
Operation: Electric
Grounding Mode: Grounding
Movement Mode: Plug-in Type
Samples:
US$ 300/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Diamond Member Since 2021

Suppliers with verified business licenses

Manufacturer/Factory
  • Overview
  • PRODUCT DETAILS
  • TECHNICAL PARAMETER
  • THE USE OF CONDITIONS
  • RELATED PRODUCTS
  • COMPANY INFORMATION
  • Contact Us
  • FAQ
Overview

Basic Info.

Model NO.
FKN12A
Number of Poles
Three Pole
Grounding
Single Ground
Series
Three
Run
Turn the Horizontal
Switching Mode
Single Throw-in
Common Model
Kfn12A
Structure of Operating
Electric
Certification
ISO, CE, ISO9001, CCC
Brand
Zhegui
Product Name
Load Break Switch
Orign of Place
Zhejiang ,China
Related Voltage
12kv
Rated Frequency
50Hz
Rated Current
up to 630A
Certificate
ISO CCC IEC
OEM
Offered
MOQ
1PCS
Filth Level
2
Mechanical Life
2000times
Transport Package
Wooden Case
Specification
230*158*210
Trademark
Zhegui Electric
Origin
Zhejiang, China
HS Code
8535900090
Production Capacity
50pieces/Week

Product Description

12kv 630A Load Break Switch Load Breaker
PRODUCT DETAILS
12kv 630A Load Break Switch Load Breaker

high voltage load switch -- fuse combination

Description:

        FKN12A-12D/T630-20 indoor high voltage pneumatic load switch-fuse combination (hereinafter referred to as FKN12A-12D load switch) is three-phase high voltage switchgear with rated voltage of 12kV and rated frequency of 50Hz, which is used for the separation and combination of load current, closed-loop current, no-load transformer and cable charging current. Turn off the short circuit current. Load switch equipped with ground switch can withstand short circuit current. FKRN12A-12D/T125-31.5 AC high voltage load switch-fuse combination is indoor high voltage switchgear combined with FN12A-12D load switch and Sport LAJ-2 (XRNT-10) high voltage current-limiting fuse. It can reliably turn on any current up to the short-circuit current, the load switch turns on the working current, the fuse turns on the short-circuit current, and the fuse turns on any overcurrent between the working current and the full short-circuit current. At the same time, the fuse switches off the load switch through its impinger.
12kv 630A Load Break Switch Load Breaker

 

TECHNICAL PARAMETER

 12kv 630A Load Break Switch Load Breaker
The technical parameters of the form are for reference only. 
Customized products can consult online customer service!
No. project units FKN12A-12D FKRN12A-12D
1 The rated voltage KV 12 12
2 Rated frequency Hz 50 50
3 Rated current A 630 125
4 Rated insulation level 1min power frequency
withstand voltage
Against the ground, phase KV 42 42
  The isolation of fracture KV 48 48
  Lightning shock withstand
voltage (peak)
Against the ground, phase KV 75 75
  The isolation of fracture KV 85 85
5 Load switch KA 20 -
  Grounding switch KA 20 20
6 Load switch S 4 -
  Grounding switch S 2 2
7 Rated short circuit closing current (peak) KA 50 -
8 Rated breaking current Active load breaking current A 630 -
  Closed-loop breaking current A 630 -
  5% active load breaking current A 31.5 -
  Cable charging current A 10 -
  Turn off the no-load transformer capacity KVA 1250 1250
9 Rated short circuit breaking current (current limiting fuse) KA - 31.5
10 Rated transfer current A - 1200
11 Mechanical life next 2000 2000
12 Impactor outputs energy J - 1+0.5



 
 serial number The name of the units data
1 Fracture from mm ≥175
2 Interphase center distance mm 210±2
3 Interphase air gap mm ≥125
4 trip mm 210±4
5 Overtravel mm ≥40
6 The three-phase switch is not at the same time ms ≤10
7 The three-phase switch is not at the same time ms ≤5
8 Inherent tripping time of shunt trip ms 40~65
9 Main circuit resistance μΩ ≤130

12kv 630A Load Break Switch Load Breaker
THE USE OF CONDITIONS
12kv 630A Load Break Switch Load Breaker

Air temperature: -25ºC~+40ºC;
Altitude: not more than
1000m;
Relative humidity: daily mean no more than 95%, monthly mean no more than 90%.
Earthquake intensity: no more than 8 magnitudes;
Installation place: no fire, explosion danger, chemical corrosion and violent vibration place;
Filth level: 2.



RELATED PRODUCTS
 

 

12kv 630A Load Break Switch Load Breaker
 

COMPANY INFORMATION

12kv 630A Load Break Switch Load Breaker    Zhejiang ZheGui Electric Co., Ltd established in 2013. We are located in Zhejiang with convenient transportation access and developed electrical market. We are group of private enterprises that hold the production license issued by the former ministry of energy and ministry mechanical and electrical engineering. 
    The company has nearly 60 million fixed assets and more than 60 employees, covering 23133 square meters. We are specialized in R&D production of complete switchgear of high and low voltage equipment such as prefabricated substation, distribution cabinet/box, drawer cabinet, ring network cabinet, inflatable cabinet, etc. 
    We owns three CNC bending machine, CNC shearing machine, CNC laser cutting machine and a series of advanced production equipment to further optimized the product structure and improve the efficiency of production. After nearly 7 years of development, it has passed ISO 9001-2000 quality system certification. All items produced by our own factory, so our advantages are: reliable quality and reasonable price. Gather the world's energy to delight your business. It's honorable for Zhegui to share your progress, brilliance and success!

 

12kv 630A Load Break Switch Load Breaker

Contact Us

12kv 630A Load Break Switch Load Breaker

 

FAQ
12kv 630A Load Break Switch Load Breaker

Q1: Are you a factory or trading company
A1: We are a factory, we can guarantee our price is first-hand, very cheap and competitive.

 

Q2: How does your factory do regarding quality control?
A2: All the products will be 100% checked before the shipment.

 

Q3: When can I get the price?
A3:Usually we quote within 24 hours after we get your inquiry.

 

Q4: How could I get a sample?
A4: if you can not buy our product in your local area, we will ship a sample to you. You will be charged a sample price plus all related shipping costs. Express delivery charge depends on the quantity of the samples.

 

Q5: What is the price of shipping?
A5: Depending upon the port of delivery, prices vary.

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now